Model |
WD1-100 |
WD1-120 |
WD1-150 |
||||||
Maximum Continuous Working VoltageUc(V~) |
420V |
385V |
275V |
420V |
385V |
275V |
420V |
385V |
275V |
Voltage Protection level Up(KV) |
≤2.4 |
≤2.2 |
≤2.0 |
≤2.6 |
≤2.4 |
≤2.2 |
≤2.6 |
≤2.4 |
≤2.2 |
Maximum discharge current(8/20us)kA |
100 |
120 |
150 |
||||||
Nominal discharge current In(8/20μs)kA |
60 |
80 |
100 |
||||||
Response Time ns |
<25 |
||||||||
Protection class |
IP20 |
||||||||
The Cross Section of L/N Line mm2 |
25-35 |
||||||||
The Cross Section Of PE Line mm2 |
35-50 |
||||||||
Selection of fuse or circuit breaker(A) |
63A、100A、125A |
||||||||
Operating Environment℃ |
-40℃~+85℃ |
||||||||
Failure Indication |
Aging failure: green normal, red failure |
||||||||
Purpose |
Primary protection of incoming line |
||||||||
Remarks |
Other maximum continuous working voltage Uc can be customized |
Overall dimensions