Loading...

WDDY-ZJ-A

  •      

Product Description

Feature

1. Meet the requirements of the national standard GB28184-2011 Fire fighting Equipment Power Monitoring System: match with the system host, fire fighting power module, etc., and flexibly build a large capacity fire fighting equipment power monitoring system:
2 The output circuit can be flexibly expanded through the system host to meet the requirements of complex and changeable modern buildings;
3. Non open operation module is adopted, self managed in the system, and one-way information transmission to the outside:
4. Monitor the working status and fault alarm information of main and standby power supplies of all monitored equipment in real time, and transmit the working status and undervoltage alarm information to the fire control room for graphic display.

Function

1. Continuously collect the monitored two-way three-phase AC current, voltage and residual current signals and transmit them to the monitor:
2. In case of phase loss, overvoltage and overcurrent of the detected power supply, an audible and visual alarm signal will be given:
3. LCD display unit, which can display the parameter values of fire power supply in real time:
4. The fire power monitoring module communicates with the fire power monitoring host through the Rs485 communication bus.


Model

Specifications

Communication bus

Overall dimensions(mm)

WDDY-64

64

1 way

500×400×140 Wall mounted

WDDY-128

128

2 way

500×400×140 Wall mounted

WDDY-256

256

4 way

500×400×140 Wall mounted


Type

Parameter

Input power

AC220V±15%50HZ

Input power

250W

Output voltage

DC24V

Communication mode

Rs485 Communication bus

Power cord

NH-BV-2X2.5mm2

Communication line

ZH-RVS-2X1.5mm2

Communication distance

≤1000(Can be extended)

Ambient temperature

-10℃~+70℃

Relative humidity

≤95%RH(40℃±2℃)

Altitude

<4500m

Degree of protection

IP30

Display function

10 inch high-resolution color LCD, full Chinese and graphic display